When choosing the burden resistor, the engineer can create any output voltage per amp, as long as it doesn't saturate the core. Core saturation level is an important consideration when specifying current transformers. The maximum volt-microsecond product specifies what the core can handle without saturating. The burden resistor is one of the factors controlling the output voltage. There's a limit to the amount of voltage that can be achieved at a given frequency. Since frequency = 1/cycle period, if the frequency is too low (cycle period too long) so that voltage-time product exceeds the core's flux capacity, saturation will occur. The flux that exists in a core is proportional to the voltage times cycle period. Most specifications provide a maximum volt-microsecond product that the current transformer can provide across the burden resistor. Exceeding this voltage with too large a burden resistor will saturate the transformer and limit the voltage.
There are factors in the current transformer that affect efficiency. For complete accuracy, the output current must be the input current divided by the turns ratio. Unfortunately, not all the current is transferred. Some of the current isn't transformed to the secondary, but is instead shunted by the inductance of the transformer and the core loss resistance. Generally, it's the inductance of the transformer that contributes the majority of the current shunting that detracts from the output current. This is why it's important to use a high-permeability core to achieve the maximum inductance and minimize the inductance current. Accurate turns ratio must be maintained to produce the expected secondary current and the expected accuracy. Fig. 2 shows the current transformed is smaller than the input current by:
ITRANSFORMED=IINPUT-ICORE-jIMAG (1)
What about the effect the transformer will have on the current it's monitoring? This is where the term burden enters the picture. Any measuring device alters the circuit in which it measures. For instance, connecting a voltmeter to a circuit causes the voltage to change from what it was before the meter was attached. However minuscule this effect may or may not be, the voltage you read isn't the voltage that existed before attaching the meter. This is also true with a current transformer. The burden resistor on the secondary is reflected to the primary by (1/N2), which provides a resistance in series with the current on the primary. This usually has minimal effect and is usually only important when you are concerned about the current that would exist when the transformer isn't in the circuit, such as when it's used as a temporary measuring device.
Notice the four loss components in the circuit of Fig. 2. The resistance of the primary loop (PRIDCR), the core loss resistance (RCORE), the secondary DCR (RDCR) is reduced by 1/N2, and the secondary burden resistor RBURDEN is also reduced by a factor of N2. These are losses that affect current source (I). The resistances have an indirect effect on the current transformer accuracy. It's their effect on the circuit that they are monitoring that alters its current. The primary dc resistance (PRIdcr) and the secondary DCR/N2 (RDCR/N2) don't detract from the Iinput that is read or is affecting the accuracy of the actual current reading. Rather, they alter the current from what it would be if the current transformer weren't in the circuit. With the exception of the burden resistor, these loss resistors are the components that contribute to the loss in the transformer and heating.
This wasted energy is usually small compared with the power in the circuit it's monitoring. Usually, the design of the transformer and choice of the burden resistor will be within the maximum energy loss the end user can allow. As battery-operated devices come into wider use and power consumption contributes to the energy crisis — even this power may be of concern. Under these circumstances, it may require special design attention to power consumption.
Current transformers are an efficient way to measure current. Since the burden resistor is reflected to the primary by 1/N2, the resistance seen in the circuit being monitored can be very small. This allows a larger voltage to be created on the output with minimal effect on the circuit being measured. A simpler and lower-cost method to measure current is to use a sense resistor connected in series with the current. However, this method can only be used when power consumption is of secondary concern. With the more frequent use of battery-powered devices and the prevailing need to reduce power consumption, the extra expense of a current transformer can soon be recovered with use. Also, with high current or when a voltage of any magnitude is required, a sense resistor would be impractical.
No comments:
Post a Comment